I get a lot of calls to make sure that the gutter that they are using is up to code.
Auxiliary gutters examples.
There are two 4inch conduits feeding the bottom of the gutter with 4x600mcm conductors in parallel in each which pass straight through to the two 4inch nipples which connect to the bottom of the meter assembly feeding the 800 amp breaker.
We are allowed by code to fill a gutter to 20.
Sizing a gutter for the proper fit is relatively easy.
Now when determining gutter or wireway fill the sum of the cross sectional areas of all contained conductors and cables at any cross section shall not exceed 20 percent of the interior cross sectional area of the wireway.
For example what is the maximum ampacity for a 1 0 awg thw copper conductor in a metal wireway under the following conditions.
Auxiliary gutters shall not contain more than 30 conductors at any cross section unless the additional conductors are for signal 01 control circuits.
Including the 1 0 awg conductor the metal wireway contains.
The sum of the cross sectional areas of all contained conductors at any cross section of an auxiliary gutter shall not exceed 20 of the interior cross sectional area of the gutter.
Nonmetallic auxiliary gutters shall be per mitted to be installed outdoors where listed and.
The following refer to sheet metal auxiliary gutters.
This auxiliary gutter used as a pull box is 5ft long 14inches deep by 14inches in height.
Code quiz of day.
Figuring the 20 is easy for example.
In auxiliary gutters and metal wireways it is not required to derate the ampacity of conductors if the number of current carrying conductors is 30 or less.
This article covers the use installation and construction requirements of metal auxiliary gutters and nonmetallic auxiliary gutters and associated fittings.
Ampacity of conductors in auxiliary gutters.
Below is a preview of article 376.
Of its interior cross sectional area 366 22 a b this is for both sheet metal and nonmetallic gutters.
A similar change occurred in article 366 for auxiliary gutters.